Grundfos Circulating Pump with Bleed Valve Ref. 59714528 for Saunier Duval Isofast F 35 E1 Boiler
Grundfos circulation pump, code 59714528, with a visible bleeder on the body, installed in the Saunier Duval Isofast C 35 E/E1, Isofast F 35 E/E1, Isomax C28 E2, Isomax F28 E205, and Isotwin C28/F28 EA range. It circulates the water in the heating circuit; the bleeder allows for the removal of trapped air. It is replaced when the motor does not start, loses flow, or the bleeder does not expel the air.
VAT included
Consult via WhatsAppSaunier Duval boilers compatible with reference 05732500
Circulating pump with reference 05732500. Eight confirmed compatibilities: C 35 E and C 35 E1.
Proven compatibility
| Boiler model | Family | Verification |
|---|---|---|
| Saunier Duval C 35 E | Isofast | Contrasted |
| Saunier Duval C 35 E1 | Isofast | Contrasted |
| Saunier Duval F 35 E | Isofast | Contrasted |
| Saunier Duval F 35 E1 | Isofast | Contrasted |
| Saunier Duval C28 E205 | Isomax | Contrasted |
| Saunier Duval F28 E205 | Isomax | Contrasted |
| Saunier Duval C 28 EA | Isotwin | Contrasted |
| Saunier Duval F 28 EA | Isotwin | Contrasted |
Can't see your model or have questions? The printed reference takes precedence. How to check it · Send us a photo via WhatsApp.
How to check if ref. 05732500 is the part for your boiler
What determines it is not the boiler model, but the reference printed on the part you already have installed.
- Find the reference printed on the installed part and check whether it matches the catalogue reference 05732500. If it is not visible, do not identify the part from its shape alone.
- Check the full boiler model on its data plate and look for it in the model associations on this page.
- Compare the connections and physical body with the original part before installation.
- If anything is unclear, send us a photo of the marking via WhatsApp before placing your order.
Symptoms and faults that the circulator pump 05732500 resolves.
The circulation pump circulates the water in the heating circuit. These are the typical symptoms and what to do:
Common symptoms and faults
- 01
The boiler turns on and works, but the heating does not heat properly.
Cause: The pump does not move the hot water with enough force, so it does not reach the heating circuit as it should.
Check that the pump is not set to the minimum speed if it has a selector, and make sure that the shut-off valves of the installation are fully open.
- 02
Noise or vibration that is noticeable when touching the body of the pump.
Cause: This could be due to trapped air in the rotor or wear in the motor.
Open the manual bleeder of the pump and check if air comes out before clean water starts to flow.
- 03
There is still air in the circuit even after bleeding the radiators.
Cause: The pump bleeder is not properly expelling the accumulated air at the highest point of the circuit.
With the pump running, loosen the bleed screw for a few seconds and check if air comes out or if it just drips water.
- 04
There is water accumulated under the pump, in the area of the shaft or the bleed valve.
Cause: The problem could be the shaft seal or the bleed valve gasket, and it is important to identify which one is the cause.
Dry the area, turn on the boiler, and observe from which exact point the moisture reappears.
- 05
The pump does not start after the summer shutdown, it remains silent or just hums.
Cause: The rotor may have become stuck due to not having rotated for months.
Try to manually release the shaft with a screwdriver on the front screw before considering its replacement.
Fault codes from Saunier Duval that this spare part resolves.
| Code | Fault | Diagnosis and solution |
|---|---|---|
| 11 | Pump blocked | The circulating pump with bleeder (Ref. 05732500) is seized/stuck or filled with air, preventing circulation; the electronics detect the pump blockage and display 11. Check for the presence of 230 V in the pump and that the rotor spins/consumes; attempt to unblock using the front screw and bleed through the automatic bleeder. |
These symptoms can have more than one cause. If your boiler displays a fault code, send it to us via WhatsApp along with a photo of the labeling, and we'll tell you if this is the part.
Data sheet for the Saunier Duval 05732500 circulation pump.
- Catalogue reference
- 05732500
- Brand
- Saunier Duval
- Type of part
- Pumps
- Units in stock
- 5 units
- Status
- Refurbished
- Warranty
- 1 year
- Shipping
- 1-2 business days
- Return
- 14 days
Data read on the part and in the manufacturer's documentation
What we have not been able to verify does not appear here.
- Voltage
- 230V~ 50Hz
- Condenser
- 2 µF
- Degree of protection
- IP 44
- Thermal class
- TF 95 / Class H
- Maximum pressure
- 6 bar
- Current
- 0.41 A
- Absorbed power
- 95 W
- Production Code (PC)
- 0126
- The manufacturer of the boiler is Saunier Duval, but the component is made by Grundfos; it is not an original Saunier Duval part.