| F.75 | Pump fault/lack of water: when the pump starts, a sufficient pressure increase is not detected. | If the Wilo UNRS15/5-3 P pump is blocked, running slowly, or without power, the pressure sensor does not detect the increase and the boiler enters F.75; check power supply to the pump, bleed, and consult d.149 (substates: 1=pump blocked, 2=electric fault, 3=dry running, 6=no response, 7=wrong pump). |
| E125 | Circulation fault in the primary circuit. | If the Wilo UNRS15/5-3 P pump does not rotate or is seized, there is no flow, and the unit detects overtemperature/gradient; check the voltage to the pump, unblock it via the front cap, and confirm there is circulation. |
| A1 281 | Pump blocked or operating with air (the heating pump is not generating pressure). | If the Wilo UNRS15/5-3 P pump is blocked or has air, it does not generate pressure and the boiler locks with A1 281; bleed the circuit and check that the rotor turns and receives power. |