| A02 | Flame signal present with burner off. | The PCB may generate/read a false ionisation signal due to electronic fault or grounding/interference at its input. Check the electrode and wiring; if they are correct, measure the ionisation signal at the PCB input and, if it persists, replace the PCB 39819530. |
| F04 | Anomaly in the parameters of the control board. | Parameters of the PCB misconfigured/corrupted (memory/settings). Enter the technical menu, review/load correct values and confirm that the PCB saves them; if not, reprogram or replace the PCB 39819530. |
| F05 | Anomaly in the parameters of the control board. | The fan/pressure switch management is handled by the PCB; an internal fault or incorrect parameters in the PCB can trigger F05 even if the fan/pressure switch are fine. Verify parameters, voltages from the PCB, and continuity; if everything is correct, reprogram or replace the PCB 39819530. |
| F07 | Anomaly in the parameters of the control board. | Incoherent parameters recorded on the PCB. Check/adjust values in the technical menu or restore to factory settings; if it does not accept/retain changes, the PCB 39819530 is defective. |
| A23 | Anomaly in the parameters of the control board. | Configuration error on the PCB (values out of range or incorrect load). Check/rectify parameters and power/ground; if it reappears, reprogram or replace the board 39819530. |
| A24 | Anomaly in the parameters of the control board. | Incorrect configuration/parameter setting on the PCB. Check/adjust parameters; if they are not saved or the alarm persists, the PCB 39819530 is damaged or needs reprogramming. |