| F.26 | Fault: gas valve not functioning. | The stepper motor/coils of the valve do not operate and the gas block does not open; check continuity and resistance of coils, presence of control voltage at the connector, and wiring up to the PCB. |
| F.27 | Safety shutdown: incorrect flame detection. | Non-sealed gas solenoid valve allows gas to pass when it should be closed, generating a 'false flame'; check valve tightness/closure (closure test and pressure drop, verification with analyser). |
| F.28 | Start-up fault: ignition failed. | The gas valve does not open or is misadjusted and does not supply the necessary flow; check gas pressure, voltage to the valve during the ignition attempt, and adjustment/function of the gas block (e.g., test P.01/CO₂). |
| F.61 | Gas valve control fault. | Short circuit/ground in the harness to the valve or damaged coils prevent its activation; check wiring, measure coil resistance, and check for control signal from the electronics. |
| F.62 | Gas valve fault. Disconnection delay. | The valve takes time to close or remains leaking after extinguishing the flame; verify airtight closure and that the flame signal disappears when cutting off the gas, and check/correct the valve if it persists. |