Gas valve: refurbished spare part that regulates and modulates the gas flow to the burner. Useful if there are ignition faults or the flame does not modulate. Compatible with CGB-11, CGB-20, CGB-K-20 (ref. 279603699). Includes a one-year warranty and delivery within 2–4 working days in the EU.

1
Consult via WhatsApp
Delivery in 2–4 working days
1-year warranty
14-day return
Technical support

Key Data

Reference
279603699
Brand
Wolf
Type of part
Gas valves
Available units
1 unit in stock
Status
Refurbished
Warranty
1 year
Shipping
2–4 working days (EU)
Return
14 days

The same part (ref. 279603699) equips these models. Verified compatibility; check the reference before purchasing.

CGB / CGB-K (Comfortline wall-mounted)

  • CGB-11
  • CGB-20
  • CGB-K-20
  • CGB-24
  • CGB-K-24
  • CGB-35
  • CGB-50
  • CGB-K-40-35

CGS (Comfortline with accumulator)

  • CGS-20
  • CGS-24

CGW (Comfortline with tank)

  • CGW-11
  • CGW-20
  • CGW-24

Fault codes related to this part (not the entire boiler). They usually have more possible causes: first rule out electrodes, wiring/connections, and gas supply. Verified with ≥3 sources.

CodeWhat does it mean?Cause and diagnosis (this part)
20Gas valve error '1' (the flame persists for 15 s after the V1 closure command).The multigas valve (SIT Sigma 848) gets stuck or leaks in path 1: even though the PCB cuts the command, combustion continues. Check for absence of voltage in the V1 coil and persistence of flame/flow at the test point; if confirmed, replace the valve.
21Gas valve error '2' (the flame persists for 15 seconds after the V2 closure command).The multigas valve (SIT Sigma 848) does not close path 2 and the gas continues to pass after the command is cut. Verify that the V2 coil is not receiving voltage and that the flame/flow continues; if confirmed, replace the valve.
How do I know if this gas valve is the one for my boiler?
Verify the reference 279603699 printed and ensure your model is on the list of compatible ones; also compare the connections with the original part. It is a SIT part.
What is it used for?
The gas valve regulates and modulates the gas flow to the burner.
Ignition faults, does not modulate, or smells of gas?
It could be the gas valve. IMPORTANT: gas handling ONLY by an authorised technician.
Which models is it suitable for?
Part shared by various models (see Compatibility). If your model does not appear, send us a photo of the marking and we will confirm it.
Installation and recommendations
Installation and pressure adjustment by authorised technician; mandatory leak check.
What does refurbished mean and what coverage does it have?
Part removed from a boiler out of service, inspected and tested. Includes 1-year warranty and 14-day return policy. Delivery within 2–4 working days in the EU.