| F.75 | The control does not detect an increase in pressure when the pump starts (lack of water/pressure or pump/sensor fault). | If the circulator (block 0020037988) is blocked, does not start, or does not respond, the pressure sensor does not detect the expected increase and the boiler locks out with F.75; check electrical/PWM start-up, consumption, and that the rotor spins after bleeding. |
| F.23 | Safety shutdown due to excessive temperature difference between flow and return. | A blocked pump or one working at minimum power prevents circulation, increases the ΔT, and triggers F.23; check that the circulator is rotating, its consumption and flow rate, and bleed the primary. |
| F.24 | Safety shutdown due to excessively rapid temperature rise. | If the circulator of block 0020037988 is seized or has insufficient power, the water does not dissipate heat and the temperature rises quickly; check the pump's rotation/consumption, PWM signal, and bleed the circuit. |
| F.20 | Safety shutdown of the temperature limiter (overheating). | The lack of circulation due to a blocked pump in block 0020037988 causes overheating in the heat exchanger; check the start and flow of the circulator, free the shaft if it is seized, and bleed. |