| 55 | PCB not calibrated. | After replacing the PCB 7691279 or losing parameters, the boiler detects that the gas valve has not been electronically calibrated. Verify by entering the installer menu and execute the automatic calibration (or adjust F03/F12 according to the manual) and confirm that the error disappears. |
| 135 | Internal fault of the card. | Self-diagnosis of PCB 7691279 detects internal fault. Check power supply and connections; if after reset and checks the issue persists, the PCB is faulty and must be replaced. |
| 83 | Communication problem between the boiler PCB and the control unit. | Communication bus fault on PCB 7691279 (eBUS/OpenTherm) may prevent communication with the control board. Check wiring and test with a known control unit; if the issue persists, the PCB is the cause. |
| 84 | Communication problem between the boiler PCB and the control unit. | Same as E83: fault in the communication circuit of PCB 7691279 or short circuit in the bus. Check bus continuity and rule out the control board; if communication is still absent, the PCB is faulty. |
| 86 | Communication problem between the boiler PCB and the control unit. | Same as E83/E84: communication fault in PCB 7691279. Check bus and control board; if there is no improvement, replace the PCB. |
| 87 | Communication problem between the boiler PCB and the control unit. | Same as E83/E84/E86: communication interface fault on PCB 7691279. Check wiring/unit; if it persists, the PCB is the cause. |
| 168E | Internal error of the boiler PCB. | In Platinum Compact 24/24F, this code indicates an internal anomaly of the PCB. After checking power supply and external interferences, if it is not restored, the PCB 7691279 is defective. |