| The reset button flashes at 1 Hz (once per second) | 1 Hz light code that groups ignition/overheating/internal fault. | The PCB (Eurotronic printed circuit board) may fail in ignition management or signal reading and cause this pattern; check with Test D in the manual (voltages at ST2 L–N, spark/ionisation, and wiring) and, if everything else is correct, replace the PCB. |
| The reset button flashes at 4 Hz (four times per second) | 4 Hz light code for evacuation supervision/safety and sensors (pressure switch, fan, NTC, encoder connector). | A defect in the PCB can prevent correct reading of the pressure switch/NTC/fan or managing the flue safety, generating the 4 Hz; check with Test E (pressure switch pressures, fan, continuity/wiring, and 230 V/5 V at connectors) and, if everything is fine, the PCB is faulty. |
| The reset button flashes at 8 Hz (eight times per second) | 8 Hz light code associated with the operation mode switch (Min/Max position) and its circuit. | If the switch line on the board (input/UI or logic) is forced or not interpreted due to a fault in the printed circuit, it maintains the 8 Hz; check the switch itself and its wiring to the PCB, and if there are no external anomalies, replace the board. |