| E62 | Calibration request. | The PCB has been replaced or is without a service/programming key and the boiler requires recalibration; check in the TsP menu that P15/P31/P32/P33 are set to default and that the service key of the PCB is present before executing Auto Calibration. |
| E77 | Absolute current values reached. | The combustion/modulation control on the PCB may be out of tolerance; rule out installation/ionisation/grounding and, if it persists, check condensation and connections to the board or replace the PCB and recalibrate (Auto Calibration). |
| E78 | Maximum regulation current value reached. | The control electronics of the PCB can saturate the regulation loop; check wiring/ground/electrode and, if it persists, inspect the board (condensation, parameters) or replace it and perform Auto Calibration. |
| E79 | Minimum regulation current value reached. | Fault in the electronic modulation/combustion control of the PCB; rule out combustion causes and, if it persists, check connections to the board and parameters, or replace the PCB and recalibrate. |
| E80 | Problem in the electronic driver of the gas valve. | Fault in the valve driver circuit on the PCB; check wiring between the board and the valve and measure control signal; if the wiring/valve are OK, the cause is the board (replace and recalibrate). |
| E89 | Problem in the combustion feedback signal. | The PCB may misinterpret ionisation/return due to an electronic fault; after ruling out electrode/flue/gas and wiring, inspect or replace the board and recalibrate. |
| E90 | Impossible to regulate combustion. | Fault in the control electronics of the PCB among the probable causes; after ruling out combustion issues, check connections/ground and, if it persists, replace the PCB and perform Auto Calibration. |
| E93 | Unable to regulate combustion (temporarily). | The PCB is listed as a possible cause (control failure); after ruling out electrode/draught/gas valve, check the board, parameters (P15, etc.) and perform Auto Calibration or replace the PCB. |
| E94 | Possible low gas pressure or flue gas recirculation. | In addition to combustion causes, the PCB is documented as a possible origin; rule out flue/electrode/gas and, if it continues, check/replace the PCB and recalibrate. |
| E98 | SW fault, error starting the PCB. | Software/start-up error of the PCB; after reset, the indicated solution is to replace the PCB and adjust P15, then execute Auto Calibration. |
| E99 | Generic fault (electronic hardware problem of the boiler). | Hardware fault in the PCB; check power/reset and, if it persists, replace the board and calibrate according to the manual (P15 + Auto Calibration). |