| 33 | Factory settings CRC error: invalid EEPROM data from "Masterreset" (CRC error in default values). | Corruption of the EEPROM in the control board; after reset, if the code persists and the parameter plug/BCC is correct, the action indicated by the manufacturer is to replace the board. Verify 24 VAC/5 V voltages and connection of the parameter plug before replacement. |
| 31 | Burner CRC error: invalid burner EEPROM data. | Memory fault in the PCB/FA; if it persists after a reset, the manuals indicate replacing the PCB. Check wiring and power supply before replacement. |
| 30 | Boiler CRC error: invalid EEPROM data for the 'boiler' assembly. | Dataset corruption in the PCB; after a reset, if it is not corrected, the official procedure involves replacing the PCB. First, check voltages and ensure there are no pending parameterization/updates. |
| 32 | Voltage fault 24V: fault in the 24 VAC supply (check fuse on PCB in *GB). | Fault in the 24 VAC supply generated/monitored by the PCB (fuse/regulator on PCB). Measure 24 VAC at terminals and PCB fuse; if everything is correct and 32 persists, replace the PCB. |
| 99 | Internal electronic/PCB error (combustion automation system fault). | Internal fault of the control/FA on the PCB; the brand indicates checking connections (e.g., fan PWM and network) and resetting; if it persists, the PCB is faulty and must be replaced. |