| 60-80-90 | Insufficient pressure in the pressure switch or flue thermostat. | The air differential pressure switch does not close because it does not reach the required depression/pressure (blocked connections, dirty venturi, or fan without flow). Check by measuring the continuity of the micro and/or pressure with a U manometer at the pressure switch connections and inspecting the tubes/venturi. |
| 40-50-80-90 | Pressure above zero in the pressure switch or flue thermostat. | The pressure switch contact is closed at rest (poor tube connection, stuck diaphragm, or incorrect setting), so the electronics detect pressure before starting. Verify that the pressure switch is open at rest (multimeter) and that the connections are correctly crossed and clean. |
| 19 | Waiting for the pressure switch to open. | The PCB detects the pressure switch closed when it should be open before start-up (stuck contact or inverted tubes). Check the status of the micro (open continuity at rest) and the direction/cleanliness of tubes and venturi; if it remains closed, pressure switch (122160280) out of range. |
| 20 | Pressure switch closing delay. | After starting the fan, the pressure switch does not close due to lack of depression (blocked ports/venturi, fan without flow, or miscalibrated pressure switch). Check the contact closure when starting ventilation and the pressure in mbar applied to the pressure switch inlet. |