| A03 | Air pressure switch alarm (Model C.S.I.). | The air pressure switch does not close/open its contact due to lack of vacuum or internal fault, blocking the ignition cycle. Check with a U-tube manometer and micro continuity while the fan generates vacuum; inspect silicone tubes and connection in the air box. |
| A04 | Water pressure switch alarm. | The water pressure switch remains open due to insufficient pressure or a fault, preventing the start-up. Check the circuit pressure (≥1 bar approx.), bleed and check the continuity of the pressure switch; if necessary, test a temporary bridge for diagnostic purposes according to the manual. |
| E35 | Differential water pressure switch error (open contact). | The water differential pressure switch does not detect sufficient flow/differential pressure or is stuck open, causing the PCB to indicate a fault. Check the differential pressure and continuity of the pressure switch during circulation; inspect filters, pump, and possible blockages. |