| 60-80-90 | Insufficient pressure in the pressure switch or flue thermostat. | The air pressure switch does not close at the start because it does not reach the pressure differential; check continuity at its terminals during startup and inspect the tubes/venturi and ensure the fan generates the vacuum. |
| 40-50-80-90 | Pressure above zero in the pressure switch or flue thermostat. | The pressure switch remains closed when it should be open before ignition; check that it opens by applying slight overpressure/underpressure to its connections and ensure the tubes are not reversed or obstructed. |
| 19 | Waiting for the pressure switch to open. | After shutdown, the air pressure switch does not reopen (detects pressure >0) and prevents the cycle; check that the contact switches to open when the fan stops and inspect the venturi/pipes. |
| 20 | Pressure switch closing delay. | At startup, the air pressure switch does not close due to a lack of depression indicated to the diaphragm; measure continuity during the ignition attempt and check the fan, venturi, and pressure switch tubes. |