| F1 | Lockout due to ignition fault. | The gas valve does not open/modulate correctly and there is not enough flow to form/stabilise the flame; check the power supply to the solenoid valves (on/off and modulating), inlet pressure, and that the ramp delivers pressure when ignition starts. |
| F6 | Flame detection with the burner off (false flame/persistent flame). | The gas valve does not close completely and allows gas to pass, maintaining a flame when it shouldn't; check the valve's tightness at rest (manometer on the manifold) and ensure that when the demand is cut, the pressure in the manifold drops to 0 and there is no residual control voltage to the solenoid valves. |
| F10 | Fault in the control/closure of the gas valve. | Mechanical or electrical fault of the valve (coils, on/off solenoids, or control module); check coil continuity, control voltage during opening/closing, and response in self-test; if there is a stuck relay on the PCB, rule it out first. |