| F.63 | EEPROM fault | Fault in the EEPROM memory integrated in the main PCB. Check supply voltages and, if the NTC sensors and wiring are correct, the PCB is responsible and must be replaced. |
| F.64 | Electronic fault / NTC | If the NTC flow/return sensors and their wiring measure correctly, the error is due to the NTC reading circuit on the PCB (analog input/5 V). Confirm by measuring the NTC at the PCB terminals; if the reading is correct and the fault persists, the PCB is defective. |
| F.65 | Fault: PCB temperature | The electronics of the PCB reach excessive temperature (thermal condition or internal fault). Check ventilation/location and, if conditions are correct and it persists, replace the PCB. |
| F.67 | Fault: electronics/flame | The PCB does not interpret a plausible ionisation signal. After checking the electrode, cable, and earth connection, if the ionisation current is correct and the error persists, the fault is in the flame circuit of the PCB. |
| F.70 | Invalid product code (DSN) | After replacing the display and/or PCB without recoding, or with incorrect coding resistance, the PCB ends up with an invalid DSN. Verify/correct product coding according to the installation manual (DSN adjustment) and, if it is not accepted, the PCB is either not suitable or is defective. |