Junkers Cerastar Gas Valve ZWN24-7MFA23 SIT Ref. 8747003700
SIT gas valve (model 845 Sigma) for Junkers Cerastar boilers ZWN24-7MFA23 and related models. It regulates the gas flow to the burner through two solenoid valves (EV1 and EV2) of 24 V~. Maximum inlet pressure 60 mbar, maximum current 165 mA. It is replaced when the boiler fails to ignite the burner or locks due to a gas supply fault.
Junkers boilers compatible with reference 8747003700
Gas valve with reference 8747003700. 31 verified compatibilities: ZWC 24/28-1 MFA and ZWC 24/28-1 MFK.
Proven compatibility
| Boiler model | Family | Verification |
|---|---|---|
| Junkers ZWC 24/28-1 MFA | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 24/28-1 MFK | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 24/28-3 MFA | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 24/28-3 MFK | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 24-1 MF2A | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 24-1 MF2K | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 28-1 MF2A | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 28-1 MF2K | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 28/32-1 MFA | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 30/30-3 MFA | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZWC 35/35-3 MFA | Ceraclass Excellence / Comfort (ZWC) | Contrasted |
| Junkers ZSC 24-3 MFA | Ceraclass Excellence (ZSC - heating only) | Contrasted |
| Junkers ZSC 24-3 MFK | Ceraclass Excellence (ZSC - heating only) | Contrasted |
| Junkers ZSC 28-3 MFK | Ceraclass Excellence (ZSC - heating only) | Contrasted |
| Junkers ZSC 30-3 MFA | Ceraclass Excellence (ZSC - heating only) | Contrasted |
| Junkers ZSC 35-3 MFA | Ceraclass Excellence (ZSC - heating only) | Contrasted |
| Junkers ZC 24-1 MFA | Cerastar / Ceraclass (ZC - heating only) | Contrasted |
| Junkers ZC 24-1 MFK | Cerastar / Ceraclass (ZC - heating only) | Contrasted |
| Junkers ZC 24-1 MF2A | Cerastar / Ceraclass (ZC - heating only) | Contrasted |
| Junkers ZC 28-1 MFA | Cerastar / Ceraclass (ZC - heating only) | Contrasted |
| Junkers ZC 28-1 MFK | Cerastar / Ceraclass (ZC - heating only) | Contrasted |
| Junkers ZWE 23-4 A | Eurostar / Cerastar (ZWE / ZWSE) | Contrasted |
| Junkers ZWE 24-4 HA | Eurostar / Cerastar (ZWE / ZWSE) | Contrasted |
| Junkers ZWE 24-4 HK | Eurostar / Cerastar (ZWE / ZWSE) | Contrasted |
| Junkers ZWE 28-4 HA | Eurostar / Cerastar (ZWE / ZWSE) | Contrasted |
| Junkers ZWSE 23-4 MFK | Eurostar / Cerastar (ZWE / ZWSE) | Contrasted |
| Junkers ZWSE 28-4 MFA | Eurostar / Cerastar (ZWE / ZWSE) | Contrasted |
| Junkers ZWSE 28-5 MFA | Eurostar / Cerastar (ZWE / ZWSE) | Contrasted |
| Junkers ZWSE 35-6 MFA | Eurostar / Cerastar (ZWE / ZWSE) | Contrasted |
| Junkers ZWN 24-7 AE | ZWN | Contrasted |
| Junkers ZWN 24-7 KE | ZWN | Contrasted |
Can't see your model or have questions? The printed reference takes precedence. How to check it · Send us a photo via WhatsApp.
How to check if ref. 8747003700 is the part for your boiler
What determines it is not the boiler model, but the reference printed on the part you already have installed.
- Find the reference printed on the installed part and check whether it matches the catalogue reference 8747003700. If it is not visible, do not identify the part by its shape alone.
- Check the full boiler model on its data plate and look for it in the model associations on this page.
- Compare the connections and physical body with the original part before installation.
- If anything is unclear, send us a photo of the marking via WhatsApp before placing your order.
Symptoms and faults that the gas valve 8747003700 resolves.
The gas valve regulates and modulates the gas flow to the burner. These are the typical symptoms and what to do:
Common symptoms and faults
- 01
The boiler tries to ignite, a clicking sound is heard, but the flame does not appear.
Cause: One of the two solenoid valves (EV1 or EV2) is not opening correctly and gas is not reaching the burner.
Measure with a multimeter that both coils receive 24V~ at the moment of ignition before replacing the entire gas valve.
- 02
The boiler keeps locking out and needs to be reset every few cycles.
Cause: An intermittent fault in the opening of the gas valve causes the control board not to detect a stable flame and to shut down for safety.
Check if the lock always coincides with the cold start; if so, first check the condition of the ionization electrode.
- 03
The gas consumption seems higher than normal for the same feeling of warmth.
Cause: If the gas valve does not close completely between cycles, it allows some extra gas to pass through even if there is no obvious leak.
Compare the consumption with previous bills and rule out other causes (insulation, thermostat) before attributing it to the gas valve.
- 04
When measuring with a multimeter, the current in the coil does not reach the expected values.
Cause: A damaged coil inside EV1 or EV2 does not generate the necessary force to open the gas flow.
Before changing the gas valve, check that the connector is not oxidized and that the wire is not frayed, as this can also result in low current readings.
Fault codes from Junkers that this part resolves.
| Code | Fault | Diagnosis and solution |
|---|---|---|
| FA | After the gas disconnection: The flame is still detected. | The gas valve does not close tightly (leak/blockage) and the control continues to read ionisation current even though the gas has been cut off. Verify with a leak test and observe that the ionisation signal disappears when closed, and that the solenoid valve closes correctly. |
| d7 | Fault in the regulating valve. | The electronics detect a fault in the gas valve (open/shorted coils or jammed mechanism). Check control voltage and coil continuity/ohmage, and ensure the valve opens/closes by measuring pressure on the ramp. |
These symptoms can have more than one cause. If your boiler displays a fault code, send it to us via WhatsApp along with a photo of the labeling, and we'll tell you if this is the part.
Data sheet for the gas valve Junkers 8747003700
- Catalogue reference
- 8747003700
- Brand
- Junkers
- Type of part
- Gas valves
- Units in stock
- 0 units
- Status
- Refurbished
- Warranty
- 1 year
- Shipping
- 1-2 business days
- Return
- 14 days
Data read on the part and in the manufacturer's documentation
What we have not been able to verify does not appear here.
- Model
- 845 Sigma
- Code printed on the part
- 0063AS4831
- Maximum inlet pressure
- 60 mbar
- EV1 coil
- 24 V~
- Maximum current
- 165 mA
- Working ambient temperature
- -15 °C to 60 °C
- Batch and manufacturing date
- Date 11/23, batch 3114629, no. 2197