Bosch/Junkers Air Pressure Switch ZW24-1LH - Ref. 8 707 406 048
RefurbishedNeckarPressure switchesBosch

Bosch/Junkers Air Pressure Switch ZW24-1LH - Ref. 8 707 406 048

Stock · 4 units

The Bosch/Junkers ZW24-1LH - 707 406 048 air pressure switch controls the pressure in the boiler system, allowing it to operate properly. When it fails, the boiler may not start or may lock out, even if the pressure is correct, which can manifest with fault codes C1, C4, or C6. This part is compatible with several boilers from the Junkers Euroline range, such as the ZW23-1AE23, ZW24-1LH AE23, among others. It is recommended to replace the pressure switch when these symptoms or operational errors are detected.

VAT included

Compatibility

Neckar boilers compatible with reference 8738709736

Pressure switch with reference 8738709736. 18 verified compatibilities: ZW23-1AE23 and ZW23-1AE31.

Proven compatibility

Boiler modelFamilyVerification
Neckar ZW23-1AE23Junkers Euroline (ZW23 / ZW24)Contrasted
Neckar ZW23-1AE31Junkers Euroline (ZW23 / ZW24)Contrasted
Neckar ZW23 AE 31 S2805Junkers Euroline (ZW23 / ZW24)Contrasted
Neckar ZW24 AE 23 S2805Junkers Euroline (ZW23 / ZW24)Contrasted
Neckar ZW24 AE 31 S2805Junkers Euroline (ZW23 / ZW24)Contrasted
Neckar ZW24-1LH AE23Junkers Euroline (ZW23 / ZW24)Contrasted
Neckar ZS23-1AE23Junkers ZS23 (AE / Euromaxx)Contrasted
Neckar ZS23-1AE31Junkers ZS23 (AE / Euromaxx)Contrasted
Neckar ZS23 AE 23 S2805Junkers ZS23 (AE / Euromaxx)Contrasted
Neckar ZS23 AE 31 S2805Junkers ZS23 (AE / Euromaxx)Contrasted
Neckar ZW20-1AME23 S2805Junkers WT/WTD water heaters and ZW20Contrasted
Neckar ZW20-1AME31 S2805Junkers WT/WTD water heaters and ZW20Contrasted
Neckar WT11 AM1E 23 S2805Junkers WT/WTD water heaters and ZW20Contrasted
Neckar WT11 AM1E 31 S2805Junkers WT/WTD water heaters and ZW20Contrasted
Neckar WT14 AM1E 23 S2805Junkers WT/WTD water heaters and ZW20Contrasted
Neckar WT14 AM1E 31 S2805Junkers WT/WTD water heaters and ZW20Contrasted
Neckar WTD14 AM1E 23 S2805Junkers WT/WTD water heaters and ZW20Contrasted
Neckar WTD14 AM1E 31 S2805Junkers WT/WTD water heaters and ZW20Contrasted

Can't see your model or have questions? The printed reference takes precedence. How to check it ·

Guide

How to check if ref. 8738709736 is the part for your boiler

What determines it is not the boiler model, but the reference printed on the part you already have installed.

  1. Find the reference printed on the installed part and check whether it matches the catalogue reference 8738709736. If it is not visible, do not identify the part from its shape alone.
  2. Check the full boiler model on its data plate and look for it in the model associations on this page.
  3. Compare the connections and physical body with the original part before installation.
  4. If anything is unclear, send us a photo of the marking via WhatsApp before placing your order.
Diagnosis and fault codes

Symptoms and faults that the pressure switch 8738709736 resolves.

The pressure switch controls the air or water pressure to authorize operation. These are the typical symptoms and what to do:

Common symptoms and faults

  • 01

    The extractor starts and sounds normal, but the boiler does not ignite the flame.

    Cause: The differential pressure switch does not detect enough pressure difference between its terminals and does not send the signal to continue.

    Check that the two silicone tubes of the pressure switch are properly connected, without cracks or disconnections.

  • 02

    A fault code for the fan or pressure switch appears even though the extractor is functioning correctly.

    Cause: If the extractor is in good condition, the problem is usually with the pressure take-off, which may be blocked by dust or condensation.

    Carefully blow out the pressure tubes and clean the connections before replacing the component.

  • 03

    The boiler fails more in winter or at low temperatures than in summer.

    Cause: The cold causes condensation in the connection pipes, which partially blocks the pressure signal to the pressure switch.

    Check for water droplets inside the silicone tubes when disconnecting them.

  • 04

    The fault is intermittent: some days it starts up properly and others it gets stuck on the first attempt.

    Cause: This is a typical symptom of a partial obstruction in the flue duct or in the pressure take-off, which varies with the draft.

    Check the condition of the flue gas outlet duct and its external terminal, not just the pressure switch.

Fault codes for Neckar that this part resolves.

CodeFaultDiagnosis and solution
C1The differential pressure switch has been activated during operation.The air pressure switch opens during operation due to a fatigued diaphragm, stuck contacts, or incorrectly connected/blocked pressure ports/hoses. Verify by measuring continuity between C and NO and the Δp with a micromanometer while the fan is running.
C4The differential pressure indicator does not open with the fan disconnected.The pressure switch remains closed at rest due to a seized diaphragm, incorrect adjustment/calibration, or improperly mounted Pitot tube/hoses. Check that with the fan stopped, the C–NO contact is open and inspect/clean the pressure switch inlets and hoses.
C6The differential pressure switch does not close.The minimum Δp is not reached or the micro does not switch due to a damaged diaphragm/faulty pressure switch or obstructed ports. Check for electrical closure between C and NO when the fan starts and measure the pressure drop at the pressure switch ports; if it does not switch within its threshold, replace it.

These symptoms can have more than one cause. If your boiler displays a fault code, send it to us via WhatsApp along with a photo of the labeling, and we'll tell you if this is the part.

Technical data

Neckar 8738709736 pressure switch datasheet

Catalogue reference
8738709736
Brand
Neckar
Type of part
Pressure switches
Units in stock
4 units
Status
Refurbished
Warranty
1 year
Shipping
1-2 business days
Return
14 days

Data read on the part and in the manufacturer's documentation

What we have not been able to verify does not appear here.

Type
Diff.Press switch Type K 132
Factory code
8 707 406 048
Batch (FAB. NR.)
985
Maximum pressure
Pa max. 20mbar
Power supply
0.1A 24V=DC
Before purchasing
  • The boiler model "Neckar NW24" listed today in the catalog does not appear in the verified list of compatible boilers; please check the exact model of your boiler.
Frequently Asked Questions

Frequently asked questions about the pressure switch 8738709736

Is the Bosch/Junkers air pressure switch Ref. 8 707 406 048 compatible with any boiler from the Junkers Euroline range?
Yes, it is compatible with models from the Junkers Euroline range such as ZW23-1AE23, ZW23-1AE31, ZW24 AE 23 S2805, and ZW24-1LH AE23.
What fault does the air pressure switch of the Bosch/Junkers ZW24-1LH resolve?
Check the pressure of the extractor before the burner ignition; if it fails, the boiler does not ignite properly.
What is the maximum pressure that the air pressure switch of the Junkers Euroline range can handle?
It accepts a maximum pressure of 20 mbar, according to the product label.
How many models are compatible with the Bosch/Junkers air pressure switch Ref. 8 707 406 048?
The total number of confirmed compatible models is 18.
What fault codes are documented for this pressure switch?
The documented fault codes are C1, C4, and C6.
Where can I find more information about the pressure switch reference?
You can look up the reference PCNZW24 for more details about this pressure switch.

Spare parts related to Neckar Junkers WT/WTD water heaters and ZW20.

Delivery 1–2 daysworking days, mainland Spain
1-year warrantyreviewed and tested
14-day returnuninstalled parts
Technical supportwe verify your model
Bosch/Junkers Air Pressure Switch ZW24-1LH - Ref. 8 707 406 048